OVPF-1M fire protection cover.
printable versionFire protection composition for metal constructions, increases fire resistance limit of steel construction up to 2.5 hours.
TU 1523-025-47935838-2003
Fire Safety Certificate SSPB.RU
Compliance Certificate GOST R
Sanitary Expertise
Application Manual
Quality Certificate
Parameter | Standard |
Composition Appearance | Uniform thick of gray color |
Cover Appearance | Uniform, without flows or scaling, gray color |
Density, g/cm³ | 1.3 - 1.9 |
Drying time at (25±2)ºC, not more than | 48 |
Adhesion, points, not more than | 1 |
Impact strength, cm, not less than | 40 |
Fire protection properties for metal construction at 27 mm cover thickness and 44.3 kg/m² consumption, hour, not less | 2.5 |
APPLICATION METHOD
Before applying the cover clean the metal surface carefully from dirt, rust, layers of other metals, with the use of solvents remove grease.
Apply composition at temperatures higher than +5ºC and humidity not more than 75%.
The composition is one component and is supplied ready to use.
Apply by hand with spittle or mechanically.
TRANSPORTATION AND STORAGE REQUIREMENTS
VPF-1M fire protection cover is not hazardous and can be transported by any kind of covered vehicle.
Storage requirements must be observed during transportation.
The cover is supplied in metal or plastic buckets which are placed on a pan fixed with a thermal shrinkage film.
Keep OVPF-1M fire protection cover at temperatures not less than +5ºC and relative humidity up to 75%.
WARRANTED PERIOD
Warranted period in case storage requirements are observed is 1.5 years on condition the cover is kept in original closed containers. The term of service is not less than 15 years on condition the application and use requirements are observed.