PK A-type therma universal cable duct filler.
printable versionEnvironmentally friendly and effective filler for cable duct. PK-A-Type THERMA is designed for increasing up to 90 min the fire resistant limit of cable duct.
TU 5789-029-47935838-2003
Fire Safety Certificate SSPB.RU
Sanitary Expertise
Application and Mounting Manual
Application and Mounting Manual(with mineral cotton wool plate Beton element Batts).
Quality Certificate
Parameter | Standard |
Prepared composition appearance | Dark green substance |
Wall cover appearance | Dark green film |
Volume mass of the prepared composition, g/cm³ | 1.3 - 1.9 |
Drying time at (25±2)ºC, hour more than | 48 |
Dry components; residue on the sieve with 1.0 mm mesh, 5, not more than | 5 |
Fire protection properties according to NPB 237-97 fire resistance limit for the cable duct, min, not less than | 90 |
APPLICATION METHOD
Clean the surface from dirt, rust, layers of other materials, then remove grease.
Apply PK-A-Type THERMA composition at temperatures higher than +5ºC and humidity not more than 80%.
The composition is two-component, mix the solid and the liquid parts before use.
Cut four fragments from the mineral wool plate to fit the size of the wall (floor) opening, two 50 mm fragments and two 25 fragments. In all the fragments cut out holes to mount them on the partition. Apply a 1 - 3 mm thick layer of PK-A-Type THERMA on the plate. Composition consumption is 3 - 5 kg per 1 m².
TRANSPORTATION AND STORAGE REQUIREMENTS
PK-A-Type THERMA composition and mineral wool plate are not hazardous and can be transported by any kind of covered vehicle. Storage requirements must be observed during transportation.
WARRANTED PERIOD
Warranted period for the composition is 12 months since manufacturing date. The term of service of the cable duct is not less than 15 years.